PUD Cross Connection Construction Plans Review Resource Documents
PUD Cross Connection Construction Plans Review Resource Documents
Last Content Update:
Overview
Domestic services will require Double Check Assemblies or Reduced Pressure Zone Assemblies. (This will be determined by the processes that will be present on site.)
Irrigation services require Reduced Pressure Zone Assemblies.
Fire protection services will require Double Check Detector Check Assemblies.
Approved installations examples can be viewed in the Cross Connection Manual.
Any backflow device installed below the ground shall have an oversized box.
The box shall have a bed of gravel and the device at least 1 inch above the gravel.
A vault shall have a 4-inch bed of gravel supporting the vault.